Summary from the notice
SLAC National Accelerator Laboratory is operated by Stanford University for the Department of Energy. As a management and operating contractor, subcontracts awarded by the Laboratory are not Federal procurements, and are not directly subject to the Federal Acquisition Regulations in 48 CFR.
Nonetheless, certain Federal laws, Executive Orders, and regulations may affect our DOE approved purchasing system, as required by statute, regulation, or contract terms and conditions. Please review the requirements and provide your best and final offer for both price and lead-time.
The following has been attached for you to complete and review: (BAA) Buy American Act Certification Representations & Certifications Rider Confirm attached SLAC Terms and Conditions are accepted Technical Specifications Requested for Quote: Modular, remotely controllable DC power supply system for detector electronics Quantity: 1 EA Please provide a price and lead time quotation by Monday, November 30, 2026.
Read full notice
Technical Evaluation Factors Listed Below: Ability to Meet the Technical Requirements: The Offeror’s proposal and supporting technical documentation will be evaluated to confirm compliance with the required detector power-supply specifications listed below. Schedule and Delivery Date: The University will evaluate the proposed lead time and delivery schedule against SLAC’s required project schedule.
An acceptable lead time is within 30 weeks after issuance of the purchase order. Past Performance: The University may evaluate documentation demonstrating prior manufacturing and delivery of similar or comparable equipment. Offerors with no relevant past or present performance history may receive an “Unknown Confidence” rating.
Required item(s) are listed below: Modular, remotely controllable DC power supply system for detector electronics Quantity: 1 EA Technical Requirements: Provide stable, low-noise, programmable DC power over at least the 30–60 VDC range. Support detector loads requiring up to 13.5 A and approximately 650 W per required output or load group.
Support multiple independently controllable outputs, with the final number of outputs determined by the detector configuration and support for up to 16 outputs where applicable. Outputs shall be electrically isolated/potential-free where required by the detector grounding scheme.
Provide programmable voltage and current limits, ramp rates, trip thresholds, temperature protection, and configurable fault behavior, including individual-channel and grouped-channel shutdown where needed to protect detector electronics. Output noise and ripple shall be sufficiently low for sensitive detector operation. Vendors shall provide guaranteed ripple and noise specifications with measurement conditions.
Ethernet-based remote monitoring and control are required, including readback of voltage, current, status, fault state, and temperature or over-temperature status. A local service/configuration interface is required. Web interface and SNMP support are specifically required for SLAC controls integration.
The system shall be air-cooled, protected against over-temperature conditions, and suitable for continuous operation at rated load in the intended SLAC installation environment. Operate from SLAC-compatible AC mains power, nominally 100–240 VAC, 50/60 Hz, with appropriate power factor correction and compliance with applicable electrical safety and EMC standards.
The system shall be compatible with standard SLAC rack or detector support installations. Standard 19-inch rack mounting is required if installed in existing SLAC racks. A compact form factor, such as 3U height or less and approximately 450 mm depth or less, is preferred unless the final installation envelope requires these limits.
Vendors shall provide mechanical dimensions, weight, cooling requirements, power input requirements, output connector details, isolation ratings, safety certifications, and remote-control interface documentation. Redundant output cap…
More open bids like this
-
Power Supply
DEPT OF DEFENSE -
Grid Research Integration and Deployment Center Technology Collaborations for US Power Electronics Industries
ENERGY, DEPARTMENT OF -
Grid Research Innovation and Development Center Technology Collaborations for US Power Electronics Industries
ENERGY, DEPARTMENT OF -
Power Supply Set
DEPT OF DEFENSE -
Euro-Diesel Drups (Diesel Rotary Uninterruptible Power Supply)
DEPT OF DEFENSE